RAC SERVER ROOM WALL SYSTEMS

Server rooms have special requirements because of the serious consequences of data loss and high heat output. from the equipment. Most air conditioning contractors are familiar with the problems of fitting basic comfort cooling systems in these applications where system failures, water leaks due to coil freeze up and panic phone calls from their customer in the early hours of the morning have been an occupational hazard.

Panasonic have developed the server room system in order to resolve these problems and they feature

  • Reliable 24/7 operation
  • Low ambient cooling operation, down to -20C using a dc inverter outdoor fan
  • A wired controller which the customer cant lose (well - lose easily at least!)
  • Extra sensors to prevent the coil freezing
  • High durability roller bearings on the fan
  • High energy efficiency to keep running costs low
  • An optional control interface to control two units for run and standby with duty sharing
  • Will do its nominal capacity at UK conditions with around 076 SHR

Server Room Wall systems

 Model Cool  Heat SEER/SCOP MCBPower  IC CablePipes  Run/Lift RRP*
 CS-E9PKEA 2.5KW3.4KW A++A+ 13A Indoor4x1.5mm  1/4" 3/8" 15m 5m £965
 CS-E12PKEA 3.5KW4.0KW A++A+ 13A Indoor4x1.5mm 1/4" 3/8"  15m 5m £1,107
 CS-E15PKEA 4.2KW 5.4KW A++A 13A Indoor 4x1.5mm 1/4" 3/8" 15m 15m £1,260
 CS-E18PKEA 5.0KW 5.8KW A++A+ 16A Indoor 4x2.5mm 1/4" 1/2" 20m 15m £1,400

* Prices exclude delivery, installation and VAT

Performance data at UK conditions

Total and sensible cooling figures below are at 24C/17C db/wb air entering the indoor unit and in a 30C ambient

 ModelNominal Cooling Total Cooling Sensible Cooling Input Power 
 CS-E9PKEA 2.5KW 2.5KW 1.9KW 0.47KW
 CS-E12PKEA 3.5KW 3.5KW 2.6KW 0.80KW
 CS-E15PKEA 4.2KW 4.2KW 3.2KW 1.10KW
 CS-E18PKEA 5.0KW 5.0KW 3.8KW 1.32KW


Optional run and standby control Interface to control two systems

The optional run and standby control interface for connecting two units together is an extra £200 plus VAT